| Main
Category |
Time Delay Relay |
| Sub
Category |
Delay on Break |
| Input Voltage |
24 VAC/VDC |
| Timing Range |
3.0 - 300 sec |
| Mounting |
.187 in. quick connect terminals |
| Contact Configuration |
2C DPDT |
| Output Current |
12 Amp |
| Function |
Off Delay |
| Compatibility |
On Off Delay units, do not use a solid state switch to initiate the timing sequence-problems with leakage current could occur. |
| Function Description |
OFF DELAY |
| Life |
Mechanical: 10,000,000 operations • Full Load: 30,000 operations |
| Load (Burden) |
3 VA |
| Output Contacts |
DPDT 12A Resistive @ 240V AC/ 30V DC, 1/2HP @240VAC |
| Repeat Accuracy |
> 2 Seconds Delay +2% • 0.1 - 2 Seconds Delay +5% |
| Recycle Time |
0.1 Seconds |
| Setting Accuracy |
Maximum Setting: +10%, -0% • Minimum Setting: +0%, -50% • Fixed Time Delay: > 2 Seconds +2%, 0.1 - 2 Seconds +5% |
| Temperature |
-28° to 65°C (-18° to 150°F) |
| Transient Protection |
10,000 volts for 20 microseconds |
| Triggering Off Delay Timers |
Timing sequence must be initiated only after input power is applied to unit. Minimum required trigger switch closure time is 0.1 seconds. |
| Voltage Tolerance |
AC Operation: +10/-15% of nominal at 50/60 Hz. • DC Operation: +10/-15% of nominal. |