| Main
Category |
Time Delay Relay |
| Sub
Category |
Multi-Function |
| Input Voltage |
120 VAC/VDC |
| Timing Range |
50 ms - 999 hour |
| Mounting |
11 Pin Octal |
| Contact Configuration |
2C DPDT |
| Output Current |
10 Amp |
| Function |
Multi-Function |
| Compatibility |
Do not use a solid state switch to initiate the timing sequence problems with leakage current could occur. |
| Function Description |
MULTI-FUNCTION (5 Field-Selectable Functions in one unit) On Delay / Off Delay / Interval On / Single Shot / Flasher |
| Insulation Voltage |
2,000 volts |
| LED |
Flasher Mode: Flashes during ON time; continuous on during OFF time All Other Modes: Flashes during timing; continuous on after time out. |
| Life |
Mechanical: 10,000,000 operations Full Load: 100,000 operations |
| Load (Burden) |
3 VA |
| Maintain Function Time |
(Time unit continues to time after power is removed) 0.01 Seconds for all units |
| Output Contacts |
DPDT 10A @ 240V AC/28V DC, 1/2HP @ 240V AC, 1/3HP @ 120V AC B300 & R300; AC15 & DC13 |
| Repeat Accuracy (constant voltage and temperature) |
+0.1% of set time or +0.02 seconds, whichever is greater. |
| Reset Time |
On Delay/Interval/Flasher: 0.1 Seconds Off Delay/Single Shot: 0.04 Seconds |
| Setting Accuracy |
+1% of set time or +50ms, whichever is greater. |
| Start-up Time |
(Time from when power is applied until unit is timing) 120 & 240V units 0.05 Seconds 12, 24 & 48V units 0.08 Seconds |
| Temperature |
12-120V Input Voltage: -28° to 65°C (-18° to 150°F) 240V Input Voltage: -28° to 50°C (-18° to 122°F) |
| Triggering Off Delay, Single Shot or Watchdog Units |
Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.1 seconds. |
| Voltage Tolerance |
AC Operation: +10/-15% of nominal at 50/60 Hz., DC Operation: +10/-15% of nominal. |