Features and Benefits

Continuous NGR monitoring Detects resistor failure within seconds, reduces transient-overvoltage risk, removes risk of ground-fault-detection failure
Shorted NGR detection Detects a ground fault on the neutral that could bypass the resistor, ensures fault current is not higher than expected
Ground-fault detection Main or backup protection to detect a ground fault anywhere on the monitored system
Adjustable pickup (2-100%) Select greatest sensitivity without false operation, adjustable in 1% increments (MEM setting)
Adjustable time delay (0.1 - 10 s) Adjustable trip delay allows quick protection and system coordination
Universal CT compatibility Allows the use of a CT that gives required ground-fault settings
Programmable output contacts Two programmable Form C and One programmable Form A (Ground Fault, Resistor Fault, Unit Health)
Selectable contact operating mode Selectable fail-safe or non-fail-safe operating modes allows connection to shunt or undervoltage breaker coil or alarm circuit (K1, K2, and K3 output contacts)
Analog output (4 - 20 mA) Connect an optional PGA-0520 meter or control system
Pulsing output (SE-330 only) Control the operation of a pulsing ground-fault-location circuit
Trip records On-board 100-event (with date and time) recorder helps with system diagnostics
Harmonic filtering (DFT) Eliminate false trips due to harmonic noise from ASDs
Local communications Mini USB port to view measured values, configure settings, and check event records
Data logging On-board microSD card (included) can be used for long-term data logging
Network communications Remotely view measured values and event records, reset trips, and cause a remote trip Available Protocol Options:
IEC 61850 - with dual RJ45, SC Fiber and RJ45, or Dual SC Fiber Interface
Modbus TCP and Ethernet/IP - with dual RJ45, SC Fiber and RJ45, or Dual SC Fiber Interface
DeviceNet - with CAN interface
Software PC-interface software (SE-MON330) is available at Littelfuse.com/RelaySoftware
Selectable reset mode Selectable latching or auto-reset operation
Unit-healthy output Verifies SE-330 is operating correctly, available as Form A or Form B output contact
Conformal coating Internal circuits are conformally coated to protect against corrosion and moisture

Documents and Downloads

Document File Type File Size Download
SE-330, SE-330HV SERIES Datesheet PDF 435 KB