Macromatic TCF-A Series products monitor for over temperature and seal leakage on
submersible pumps with 3-wire sensing (resistive seal, N.C. over temp). Product can be installed
in place of existing Flygt MiniCAS with minimal rewiring. These units come with a switch to select
either automatic reset or manual reset for an over temperature condition.
The ange-enclosure is designed to be mounted on an inner door and used with a back-mounted
socket (included). Product can also be DIN-rail mounted using socket 70170-D (not included).
Everything needed for setup, use and troubleshooting is on the top of the unit: status LEDs,
switch to choose Automatic or Manual Reset mode for temperature, and a pushbutton for Manual
Reset of an over temperature condition. They are all visible so that the door need not be opened
to see the status of the over temperature or seal leakage condition.
Operation:
A normally closed thermal switch in the windings of the pump motor is connected to the TEMP
input to monitor for overheating of the pump. A low-voltage DC signal is applied to monitor
the thermal switch. The pump seal leakage sensor(probes) are connected to the LEAK input
to monitor for seal leakage using a low-voltage DC signal. Isolated output contact relays are
provided, one for over temperature and one for seal leakage. The over temperature trip point is
xed at 5K ohms. Adjustable seal leakage sensitivity range is 4.7K-100K ohms.
With input voltage applied, normal temperature condition (thermal switch closed) and seal
leakage above the sensitivity set-point, the over temperature relay is energized and the seal
leak relay is de-energized. Both LEDs are Green, indicating normal conditions and input voltage
applied. When motor temperature rises and the N.C. thermal switch opens, the over temperature
relay is de-energized opening the contact that had been closed turning off the pump contactor.
The TEMP LED turns Red. If the over temperature condition is cleared, the unit will reset based
on the setting of the AUTO-MANUAL RESET switch. In the AUTO mode, the unit will reset
automatically. In the MANUAL mode, the Over Temp Reset button must be pushed to clear
the alarm and reset the relay. (Note: If fault still exists when the Over Temp Reset button is
depressed, it will not reset.)
If the shaft seals start to leak, contaminating uid enters the pump motor cavity. This lowers the
resistance of the lubricant inside the pump. When the resistance drops below the user-adjustable
sensitivity set-point of the relay, the output relay energizes and closes a contact, which can be
used to give an alarm indication of a leaking seal. The LEAK LED turns Red. If the seal leak
condition is cleared, the unit will reset automatically.
If either a TEMP or SEAL leak alarm has been automatically cleared, a cleared fault indication
is displayed by ashing the corresponding Red TEMP LED or Red
Features
- Monitors Submersible Pumps for Over Temperature & Seal Leakage
- Retrofits Flygt controls for pumps with 3-wire sensing
- Auto & Manual Reset for Over Temperature
- Flange Enclosure for Door-Mounting
- DIN-Rail mounting available using 70170-D socket
- Low-Profile Adjustment Switch & Reset Button
- Full Status Indication on Top of Unit for Easy Troubleshooting
- 11 Pin Back-Mounted Socket Provided with Relay